Controller Double setpoint
ATR 141
Controller 32x74mm, Single control loop, 4-digits Display. Distinctive feature is the high configurability, resulting in a limited number of ordering codes.
Universal analogue input, selectable for a wide range of sensors, both for industrial or civil applications. Relay/SSR outputs, programmable as command/alarm/event. Optional RS485-ModbusRTU/Slave.
User-friendly operation, programming tools for quick set-up (MEMORY-CARD, programming and monitoring software LABSOFTVIEW).
Ordering codes
ATR141-AD: 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc / Supp. 12...24Vac/Vdc
ATR141-A: 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc / Supp. 24Vac
ATR141-B: 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc / Supp. 230Vac
ATR141-C: 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc / Supp. 115Vac
ATR141-ADT: 1 Analogue Input + 1 Relay 8 A + 1 SSR 12Vdc + RS485 Modbus RTU Slave / Supp. 12...24Vac/Vdc
Main features
Box: 32x74 (front panel) x 53 mm
Power supply: 12...24 Vac/Vdc or 24Vac/115Vac/230Vac ±15% 50/60 Hz
Display: 4 digits, 0.4"red + 3 signaling leds
Operating conditions: Temperature 0-45 °C, humidity 35..95 RH%
Material: Box: Noryl UL94V1 self-extinguishing; front panel: PC ABS UL94V0 self-extinguishing
Sealing: Front panel IP65 (with gasket) , Box IP30, Terminal bloks IP20
Quick set-up options: Memory Card with / without battery, software LABSOFTVIEW
Inputs
1 configurable: Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K
(B 3435K), 0/4..20 mA, 0..10 V, Potentiometer 1...6/160 Kohm.
Sampling frequency : 66ms (frequency 15 Hz)
Outputs
2 Relays: 1 Relay 10A/8A - 250 Vac resistive charge + 1 Relay 5A - 250 Vac resistive charge
1 SSR: 8 Vdc - 20 mA (codes A/B/C) - 15 Vdc - 30 mA (code AD)
Serial communication: RS485 Modbus RTU - Slave
Software features
Control algorithms: ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportioned, Dead band
Tuning: manual or automatic
Operating modes: Visualizer, Single setpoint, Double setpoint (selection by parameter)
Data protection: Lock of control / alarm setpoint - Access to parameters by password
Alarm modes: Absolute / Threshold, band, High / Low deviation. Alarm with optional manual reset
Double P.I.D.: Heating / Cooling P.I.D.
Open / Close logic: Open / Close logic for motorized valves
|